Table 2-1. Smoke Detector Specifications
Specifications Smoke Detector Data
Detector
PID (4098)
-9601, -9605 -9602 -9603
Type of Detector
Photoelectric
Photoelectric
with Heat
Ionization
Working Voltage
(2-wire)
8.5 – 33 VDC 8.5 – 33 VDC 8.5 – 33 VDC
Rated Voltage
(4-wire)
15 – 32 VDC 15 – 32 VDC 15 – 32 VDC
Input Ripple
Voltage
25% Max. 25% Max. 25% Max.
Max. Alarm
Current
86 mA 86 mA 86 mA
Surge Current
<200 A <200 A <200 A
Standby Current
<100 A <100 A <100 A
Heat Element
Rating
N/A
135 F
N/A
Humidity Range
(Non-Condensing)
10-95% RH 10-95% RH 10-95% RH
Air Velocity
Range
0-2000 FPM 0-2000 FPM 0-200 FPM