Maintenance/Troubleshoong — 21
8 MAINTENANCE/TROUBLESHOOTING
e load bank has been designed to require minimum
maintenance. All components have been chosen for a long,
reliable life. Two basic intervals of maintenance are required:
each operation and every 6 months.
Check the air intake screens and louvers, fan and cooling
chamber, and exhaust openings for any obstructions or
foreign objects.
Check fan blades for stress fractures.
Check the exhaust vent for obstructions
Check the load branches for blown fuses or opened load
resistors.
To check the fuses or load resistors, operate the load bank
from a balanced 3-phase source and check the three line
currents. e three current readings should be essentially the
same. If a sizable dierence is noted, one or more load fuses or
load resistors may have malfunctioned.
Check the tightness of the electrical connections. e
expansion and contraction caused by load bank operation may
cause loose connections. For a detailed inspection guide, see
“Primary Inspection” on page 6.
general
maintenanCe
eaCH
o
peration
every 6
m
ontHS
Remove all
power from
the load bank
before
servicing the
unit.