2-4
This section describes how to use the DIP switches on the 4009 TrueAlert Addressable Controller
board for setting addresses and optional features.
The SLC Appliance Switches (SW1, SW2, SW3) are 8-position DIP switches. Use these switches
to set the number of appliances connected to each SLC. SW1 corresponds to SLC 1, SW2
corresponds to SLC 2, and SW3 corresponds to SLC 3. A maximum of 63 appliances or 2.5 amps
of power may be specified per SLC channel (refer to Field Wiring Diagram 842-158). Refer to
Figure 1-2 to locate the switches on the system board. Refer to Figure 2-2, below, to specify the
correct number of appliances for each SLC channel.
Use a small screwdriver or pen to set the switches.
Notes:
DIP switch in “1” position is ON while DIP switch in “0” position is OFF.
SW1, SW2, and SW3 are disabled when the RUI host interface is selected.
0000 1000 0100 1100
0000
0 163248
1000
1 173349
0100
2 183450
1100
3 193551
0010
4 203652
1010
5 213753
0110
6 223854
1110
7 233955
0001
8 244056
1001
9 254157
0101
10 26 42 58
1101
11 27 43 59
0011
12 28 44 60
1011
13 29 45 61
0111
14 30 46 62
15 31 47 63
LSB
MSB
1 2345678
1111
DIP SWITCHES 5 AND 6
DIP
SWITCHES
1 THRU 4
RESERVED FOR
FUTURE USE
NOT USED
ON
OFF
1 = ON 0 = OFF
DIPSWITCH IS SHOWN
SET AT ADDRESS 7.
Figure 2-3. SLC Appliance Settings (SW1, SW2, SW3)
Continued on next page
System Configuration
Overview
SLC Appliance DIP
Switches
(SW1, SW2, SW3)
DIP SWITCH IS SHOWN
SET AT ADDRESS 7.