3-2
Each step in this section is intended to be read sequentially, so that the last instruction from
“Step 1. Starting the Programmer,” for example, leads directly to the first instruction in
“Step 2. Adding an IDNet Point…” Read the entire section to make sure you make all the
necessary configurations.
These programming instructions can be used to:
• Add a 4009 TrueAlert Addressable Controller to a 4010
• Modify settings for already programmed 4009 TrueAlert Addressable Controllers
The instructions below describe how to log in and start the 4010 panel programmer.
1. Press the MENU button so that the display reads Menu:[Control/View Points].
Then press the NEXT button. The display reads Menu:[Login/Logout].
2. Press the ENTER button. The display reads <Enter> to [Login]. Press ENTER
again.
3. The display reads Passcode:[0]. Enter your passcode. The passcode must have
access to programming and all other menus mentioned in these instructions. Use the
PREVIOUS and NEXT buttons to select numbers 0 through 9. When you have selected
the correct number, use the right arrow button to move to the next digit. When you move
to a different digit, numbers that have already been entered will appear as asterisks (*). If
you make an error, use the left arrow button to backspace. When you are done, press
ENTER. At this point the display reads **Login is Accepted** and displays your
current access level.
4. When the display returns to normal, press NEXT until you reach
Menu: [Programming]. Press ENTER.
5. The display reads Please Wait… Fire Alarm Operation Suspended. After
a moment, it reads Press <ENTER> for Programming Press <EXIT> to
resume operation. Press ENTER.
Continued on next page
4010 Programming Steps
Overview
Step 1:
Starting the
Programmer