2-12
The following documentation may be required:
• Field Wiring Diagram 842-158
• 4009-9812 Class A Adapter Option Card Installation Instructions (574-763)
• 4009-9809 IDNet Repeater Option Card Installation Instructions (574-327)
• 4009-9810/-9811 Fiber Optic Link Option Installation Instructions
(574-182)
• 4901 TrueAlert Horn Installation Instructions (574-764)
• 4902 TrueAlert Ceiling-Mount and Wall-Mount Speaker Installation Instructions
(574-765)
• 4903 TrueAlert Ceiling-Mount A/V Installation Instructions (574-929)
• 4903 TrueAlert S/V Installation Instructions (574-766)
• 4903 TrueAlert A/V Installation Instructions (574-768)
• 4904 TrueAlert Ceiling-Mount Strobe Installation Instructions (574-928)
• 4904 TrueAlert Strobe Installation Instructions (574-767)
• 4905 TrueAlert Isolator Module Installation Instructions (574-769)
• 4906 TrueAlert Multi-Candela Notification Appliances Installation Instructions
(579-808)
• 4906 TrueAlert Multi-Candela Amber Strobe Installation Instructions (579-828)
• All wiring must be installed in accordance with local codes.
• A minimum of 6 inches (15.24 cm) of free conductor is required at each electrical box to
facilitate terminations.
• A 12-inch (30.48 cm) service loop of cable is required for all continuous pulls through an
electrical box.
• All system wiring subject to physical damage must be mechanically protected based on
the environment to which the cable is subjected.
• A neatly wired system helps assure an accurate inspection of all connections and simplify
troubleshooting.
• Field adjustments may not be made to the TrueAlert Addressable Controller board.
Continued on next page
System Installation, Continued
Required
Documentation
General Notes