2-15
AC Input - 120VAC, 3 amperes, 60Hz
Battery Input - 24VDC, 8 amperes
4009 TRUEALERT
ADDRESSABLE
CONTROLLER
(SEE
NOTE 2)
AC INPUT
POWER
EXTERNAL
BATTERY
CONNECTION
(IF REQUIRED)
IDNet
INPUT
RUI
INPUT
TO AUDIBLE AND/OR VISIBLE
NOTIFICATION APPLIANCES
TRUEALERT CHANNEL
SIGNALING LINE CIRCUITS:
THREE CLASS B/STYLE 4 CIRCUITS STANDARD
(CLASS A/STYLE 6 CIRCUITS AVAILABLE)
CIRCUITS RATED AT
2 1/2A @ 24 VDC PER CIRCUIT,
POWER LIMITED 8A TOTAL POWER AVAILABLE
#18 AWG MIN
NAC OF
HOST FACP
HARDWIRED
NAC
CONTROL
AUXILIARY
POWER
OUTPUT
Notes:
1. Refer to the Field Wiring Diagram (842-158) for detailed information on 4009 System Wiring
Configurations.
2. External Battery requires splicing into existing Battery Harness (733-945), see Note 1.
Figure 2-7. 4009 TrueAlert Addressable Controller Connection Diagram
Continued on next page
System Installation, Continued
System Power
Requirements