3-5
1. Press NEXT until you get to Programming: [Save CFIG], and press ENTER. Press
ENTER again at the prompt.
2. The display indicates the panel is saving and then restoring the CFIG and the labels.
When the system is done saving, it reboots. Your passcode is cleared from the system,
and you have to log in again if you want to continue programming (i.e., to add, edit, or
delete points).
To set audible signal types for audible notification appliances,
1. Log in and open the Programming menu.
2. Press NEXT until the Programming: System Options menu item appears. Press
ENTER.
3. Press NEXT until System Options: TrueAlert Non Adr. Horn appears,
and press ENTER.
4. Use the NEXT and PREVIOUS buttons to scroll through the list of options for TrueAlert
Non-Addressable NACs (in this case, TrueAlert SLCs) that appear in the New: field.
The choices are Temporal, Steady, and Slow March. When you make your
selection, press ENTER. Press ENTER a second time to confirm your choice.
4010 Programming Steps, Continued
Step 5:
Saving a
Configuration
Step 6:
Specifying Signal
Operation