PRODUCT SPECIFICATIONS
SKF Multilog On-line System IMx-16Plus
SKF Multilog On-line System IMx-16Plus
User Manual
Revision Letter A
3.2 SKF Multilog On-line System IMx-16Plus
3.2.1 Environmental
DIN rail mounting (35 mm x 7,5 mm ‘top hat’ DIN rail)
Size (H x W x D): 172 x 104 x 40 mm (6.8 x 4.1 x 1.6 in.)
o Height (H) across, width (W) along and depth (D) above the rail
o Height does not include terminal connectors and Bluetooth dongle
o Depth does not include the DIN-rail mounting bracket
Weight: 900 g (1.98 lb)
IP ratings:
o IP30, for the DIN rail mounted enclosure
o IP65, for the wall mounted SKF cabinets (Including HMI where
applicable)
o IP67, IP69K and IK09 for the optional LTE/GSM/Wi-Fi antenna
o IP69K for the optional GPS module
Temperature ranges
o Operating: 40 to +65 °C (−40 to +149 °F)
o Storage: 50 to +85 °C (−58 to +185 °F)
Humidity: 95% (relative) non-condensing
Measurement category II
Pollution degree 2
Maximum altitude: 2 000 m (6 562 feet)
Vibration tolerance:
4 13,2 Hz 1 mm
13,2 100 Hz 0,7 g
Number of axes: 3 mutually perpendicular
3.2.2 Power
10 W typical, 12 W maximum (but refer exception*)
o Power over Ethernet (PoE) max 13 W (nominal voltage 48 V) or
o 24 to 48 V DC (±5%)
o Connect to the lower pair of connections, see
Figure 4
o Recommended supply fuse rating: T2AL (2A slow blow)
o PoE and 24 to 48 V DC can be used redundantly
o *PoE is not available when three relay outputs and LTE/GSM
functions are all enabled
Optional CMON 4137: DIN rail mounted power supply for IMx-8/IMx-16Plus
o Universal AC input: 100 to 240 VAC (nominal)
o DC input range: 120 to 370 V DC
o Dimensions: 74 x 54 mm (2.91 x 2.13 in.) across/along the rail
3.2.3 Analogue inputs
16 analogue single ended inputs, referenced to chassis/enclosure ground.
o Input range ±25 V
o Supports 2-wire constant current sensors and/or voltage signals
o 4-20 mA signals accepted (required load resistor to be fitted at input)

Table of Contents