5.7.2 Phase codes for normal mode and alarm mode
In normal or alarm mode, the phase code corresponding to the program phase is shown on the display.
Phase code Description
dC
Waiting for pressure discharge
(disCharge)
Loc
The interlocking switch is closed
(Locked)
OFF
The channel is closed
AGr
Lubricant reservoir low level alarm
(Alarm, Grease)
ALP
Pressure low alarm (the line pressure does not rise high enough during the pressurisation time)
(Alarm, Low Pressure)
Pulse alarm (progressive system)
(Alarm Low amount of Pulses)
AHP
Alarm, high pressure
(the line pressure has not dropped low enough when the pressurisation phase starts)
(Alarm, High Pressure)
AIn
An alarm from the SKF Doser monitor doser operation indicator.
The code is used only if SKF Doser monitors are in use.
(Alarm, Indicator)
Air
An alarm from the air pressure switch of the grease spray system.
The code is used only if an air pressure switch is in use.
(Alarm, Air)
APC
A warning of a pump change when a dual pumping centre (Dualset) is in use.
(Alarm, Pump Changed)