5.7.4 Normal mode displays, progressive lubrication system
Normal mode displays, which show lubrication program setpoints, can be browsed with ù.
Display codes change in the following order when ù is pressed.
Display code Description
CH
The lubrication channel selected on the display.
Press SET to move to another channel when the code is displayed.
Cou
The lubrication cycle counter.
(Cycle Counter)
The counter reading increases by one unit when lubrication ends. A decimal point is used to
separate thousands.
C
The lubrication cycle setting value as time [h.mm] or pulses, depending on the factory setting
parameter CYC. Can be set in the range of 0 min 999 h or 000…999 pulses.
(Lubrication Cycle)
P
The maximum pressurisation time setpoint [s]. Can be set in the range of 0...999 s.
The setpoint can be changed to minutes with factory setting parameter Prt.
Can be set in the range of 0...999 min.
(Lubrication, Pressurization time)
PP1
The pulse count setting (PP1) can be 000…999.
If PP1 is set to 0, the maximum pressurisation time is always used. The pulse sensor does not need
to be connected. Alarms will not be received, except for the low limit alarm.
(Pulses per 1 pressurization)
HL
Manual operation setting
On: Manual operation mode
OFF: Automatic operation mode
PU
The pump is currently in use when the dual pumping centre (Dualset) is in use:
1: Pump 1 in use.
2: Pump 2 in use.
This parameter is only displayed when YES has been set as the value of the dUA factory setting
parameter.
Decimal points are used to separate thousands in the lubrication cycle counter reading. The counter’s max. reading is
49.9 = 49999.