38
Quick Conguration
is split into several parts. In addition, this
eld allows you to edit macros (1%-7%)
which insert the real values of the variables
instead of the text.
To send a test message press “Send sms”. The
macros in the message text will be displayed in
its original form (% ..). To save the notication
properties, click “Save”.
After lling in the properties of notication , you
must specify the event, at occurence of which
SMS notication will be sent. To do this, go to
“Preferences” >> “Logic schemes” >> “Add”
and specify the conditions for sending SMS
notications.
For each new recipient you have to repeat the
procedure of adding SMS notication.
Before messages are sent they are queued up,
which means you do not have to wait until the
previous message is sent. The information on
all SMS sent is displayed in the log of monitoring
system.
If an error occurs while sending a message, the
log displays “SMS send error” and indicates the
error number. The most common error is 515
(Ps busy), which can occur when:
• not enough credit on the SIM card;
• wrong SMS centre number;
• low signal level ( less than 15%) in the
home network;
• wrong SMS format ( the number must
begin with a “+”) or the number is invalid.
If these points do not cover your case, try to
reboot the system. In addition, try to send SMS
from your mobile phone, make sure the SMS
centre number is the same.
SMS commands
SMS-commands are used for remote control
of monitoring system. Using these commands,
you can read the state and the measured
values of sensors, control relays or outlets.
Phone numbers from which the SMS com-
mands will be sent, should be added to the list
of allowed numbers in the modem properties (
Right click on modem icon “Edit GSM modem”
>> “Allowed numbers”). In response to each
SMS-command, a response SMS will be sent.
In case of an error, an SMS will be sent with
information about the error and an example of
command. An SMS can contain only one com-
mand for only one element.
Command: reading sensor (relay, outlet)
parameters
Function. get [id] or get [name], where id –
number of the element, name – name of the
element. Field “get” is not case sensitive, both
can be used Get, GET. Field “name” is case
sensitive.
Description. This command checks the state of
SMS to the phone, from which the command
was sent.
Examples.
• “get 1034” - to obtain information about
the sensor with number 1034;
• ”Get Analog-1” - to obtain information
about the state of the element with the
name of Analog-1;
• “GET Relay-2” - to obtain information about
the state of the element with the name of
Relay-2.
Command: setting impulse of relay/outlet
Function. set [id] [name] pulse [duration],
where id – number of the element, name –
name of the element, duration – duration of