SMA Solar Technology AG Electrical Connection
Installation Guide SB13_21TL-IA-IEN121060 31
3. Ensure the cable is correctly in place.
4. Push the bolted connection toward the thread and fasten to a torque of 2 Nm.
The DC connectors are now assembled and can be connected to the inverters, as described in
section 5.4.4"Connecting the PV Array (DC)" (page33).
Result Measure
If the conductors are visible in the hollow
cavity of the clamping clip, the cable is in
the correct position.
Proceed to step 4.
If the conductors are not visible in the
hollow cavity, the cable is not in the correct
position.
Loosen the clamping clip. For this purpose,
use a screwdriver with a width of 3.5 mm.
Remove cable and start again from step 1.