SMA Solar Technology AG Electrical Connection
Installation Guide SB20_25_30HF-IEN102911 39
6.2 Connection to the Public Grid (AC)
6.2.1 Conditions for the AC Connection
Cable Sizing
The grid impedance of the AC cable must not exceed 1 Ω .
The conductor cross-section should be dimensioned such that cable losses do not exceed 1 % at
nominal power. Use "Sunny Design" (www.SMA.de/en/SunnyDesign) for this.
The maximum cable lengths relative to the conductor cross-section are shown in the following table.
Do not exceed the maximum cable length.
The conductor cross-sectional area required in individual cases depends on the following factors
among others:
Ambient temperature,
Routing method,
•Conduction losses,
valid installation requirements of the respective country (installation location).
Cable requirements
Connection requirements of the utility operator
Always observe the connection requirements of your utility operator.
Conductor
cross-section
Max. cable length
SB 2000HF-30 SB 2500HF-30 SB 3000HF-30
2.5 mm² 18 m 14.5 m 12 m
4.0 mm² 29 m 23 m 19 m
Position Description Value
A External diameter 6 mm … 14 mm
B Conductor cross-section 2.5 mm² … 4 mm²
C Strip insulation 8 mm