SMA Sunny Boy 3000US - Page 86

SMA Sunny Boy 3000US
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Displays and Messages Measuring Channels and Parameters
7-20 SMA America SB3000US-4000US-11-SE1607
h_Total h 0 ... 200000 0 Installer Total total operating hours of the
inverter. Changing the value can be
necessary when a Sunny Boy is
exchanged and you wish to match
the previously acquired data.
Memory Function no function
Default param.
Reset Op.Data
Reset errors
no function Installer Default param.: Sets all parameters
to default.
Reset Op.Data: Sets all parameters
that are visible in user level to
default values.
Reset errors: Resets all permanent
device disable errors.
Operating Mode MPP-Operation
Turbine
V-const
Stop
MPP Installer Operating Modes of the Sunny Boy:
MPP-Operation: Sets the Sunny Boy
in Maximum Power Point Tracking
Mode
V-const: Constant Voltage Mode
(Setpoint defined in “Vconst-Setval“)
Turbine: Operating mode for wind
power plants
Stop: Disconnection from utility, no
operation
T-Max-Fan °C 0 ... 100 90 Installer Temperature for maximum fan
rotation speed.
T-Start s 5 ... 1600 10 Installer The time the inverter waits to connect
to the grid after Vpv-Start is
exceeded.
This value defaults to 5 minutes after
a utility fault.
T-Start-Fan °C 0 ... 100 60 Installer Fan turn-on temperature at minimum
rotating speed.
T-Stop s 1 ... 1800 2 Installer The time that the Sunny Boy waits to
disconnect from the grid when Pac
falls below minimum necessary Vpv.
T-Stop-Fan °C 0 ... 100 50 Installer Fan turn-off temperature
V-Const Setval V SB 3000US:
185 ... 500
SB 4000US:
230 ... 600
SB 3000US:
500
SB 4000US:
600
Installer PV Setpoint voltage for constant
voltage operation. These
parameters only are important in
case the parameter “Operating
Mode“ is set to “V-const“.
Vac-Min* % 0 ... 50 12 Installer Values are used to calculate the
lower and upper limits of allowable
AC voltage
Default value is optimal for
installations < 30 kW
Vac-Max* % 0 ... 20 10 Installer
Vac-Min-Fast* % 0 ... 50 50 Installer Values are used to calculate the
lower and upper limits of allowable
AC voltage for fast disconnection.
Default value is optimal for
installations < 30 kW.
Vac-Max-Fast* % 0 ... 20 20 Installer
Name Unit Range Default Pass-
word
Level
Description