Parameter lists SMA America, LLC
162 SI5048U-TUS121440 Technical Description
#223 Battery Protection
#224 Battery Silent Mode
No. Name Description Display value Default value
01 BatPro1TmStr Starting time of the
battery-
preservation mode
(level 1)
22:00:00
02 BatPro1TmStp End time of battery-
preservation mode
(level 1)
06:00:00
03 BatPro2TmStr Starting time of the
battery-
preservation mode
(level 2)
17:00:00
04 BatPro2TmStp End time of battery-
preservation mode
(level 2)
09:00:00
05 BatPro1Soc Battery charge
state for battery-
preservation mode
level 1
0 % … 70 % 20 %
06 BatPro2Soc Battery charge
state for battery-
preservation mode
level 2
0 % … 70 % 15 %
07 BatPro3Soc Battery charge
state for battery-
preservation mode
level 3
0 % … 70 % 10 %
No. Name Description Value Explanation Default
value
01 SilentEna Silent mode on the
grid
Disable disable Disable
Enable enable
02 SilentTmFlo Maximum time for
float charge until
transfer into silent
1 h … 48 h 3 h
03 SilentTmMax Maximum time for
silent until transfer
into float charge
1 h… 168 h 12 h