SMA America, LLC Parameter lists
Technical Description SI5048U-TUS121440 165
233# Grid Start
No. Name Description Display value Explanation Default
value
01 GdSocTm1Str SOC limit for
switching on the
grid for time 1
40 %
02 GdSocTm1Stp SOC limit for
switching off the
grid for time 1
80 %
03 GdSocTm2Str SOC limit for
switching on the
grid for time 2
40 %
04 GdSocTm2Stp SOC limit for
switching off the
grid for time 2
80 %
05 GdTm1Str Time 1 for grid
request in hours,
minutes and
seconds.
Begin time 1, end
time 2.
06 GdTm2Str Time 2 for grid
request in hours,
minutes and
seconds.
Begin time 2, end
time 1.
07 GdPwrStr Grid request
starting capacity
4.0 kW
08 GdPwrStp Grid request
disconnection
power limit
2.0 kW
09 GdStrChrgMod Charging start
upon grid
connection
Off Off Equal
Full Full charge
Equal Equalize charge
Both Full and equalization
charge

Table of Contents