EasyManua.ls Logo

SMA SUNNY ISLAND 5048-US - Page 167

SMA SUNNY ISLAND 5048-US
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA America, LLC Parameter lists
Technical Description SI5048U-TUS121440 167
235# Generator Start
20 GnAlSns AI sensitivity Low Low Normal
Medium Medium
Normal Normal
High High
No. Name Description Value Explanation Default
value
01 GnAutoEna Generator autostart Off Disable On
On Enable
02 GnAutoStr Number of autostarts 3
03 GnSocTm1Str SOC limit for switching on
generator for time 1
40 %
04 GnSocTm1Stp SOC limit for switching off
generator for time 1
80 %
05 GnSocTm2Str SOC limit for switching on
generator for time 2
40 %
06 GnSocTm2Stp SOC limit for switching off
generator for time 2
80 %
07 GnTm1Str Time 1 for generator request in
hours, minutes and seconds.
Begin: Time 1,
End: Time 2
08 GnTm2Str Time 2 for generator request in
hours, minutes and seconds.
Begin: Time 2,
End: Time 1
09 GnPwrEna Generator request based on
power
Off Disable Off
On Enable
10 GnPwrStr Generator request switch-on
power limit
4 kW
11 GnPwrStp Generator request switch-off
power limit
2 kW
12 GnPwrAvgTm Average time for power-
related generator start
60 sec
13 GnTmOpEna Time-controlled generator
operation
Disable Disable Disable
Enable Enable
No. Name Description Value Explanation Default
value

Table of Contents