16 Technical Data
SMA Solar Technology AG
Operating Manual STPx0-3SE-40-BE-en-10 125
STP5.0-3SE-40 STP6.0-3SE-40 STP8.0-3SE-40 STP10.0-3SE-40
Battery type
1)
Li-ion Li-ion Li-ion Li-ion
Surge category in
accordance with
IEC60664-1
II II II II
AC output, AC battery-backup system in parallel grid operation mode
STP5.0-3SE-40 STP6.0-3SE-40 STP8.0-3SE-40 STP10.0-3SE-40
Rated power at
230V, 50Hz
5000W 6000W 8000W 10000W
Maximum appar-
ent AC power
5000VA 6000VA 8000VA 10000VA
Output power <
5min
6000W 7200W 12000W 12000W
Output apparent
power < 5min
6000VA 7200VA 12000VA 12000VA
Output power <
10s
10000W 10000W 12000W 12000W
Output apparent
power < 10s
10000VA 10000VA 12000VA 12000VA
Nominal AC volt-
age
3/N/grounding
conductor;
230V / 400V
3/N/grounding
conductor;
230V / 400V
3/N/grounding
conductor;
230V / 400V
3/N/grounding
conductor;
230V / 400V
AC grid frequency 50Hz 50Hz 50Hz 50Hz
Switching time to
battery-backup
operation
2)
< 50ms < 50ms < 50ms < 50ms
Grid configuration TN-S TN-S TN-S TN-S
Protective Devices
DC reverse polarity protection Available
Input-side disconnection point Available
AC short-circuit current capability Available
Ground fault monitoring Available
Grid monitoring Available
1)
Warning! Danger of fire due to use of non-approved batteries. Only use batteries approved by SMA
Solar Technology AG (technical information with list of approved batteries at www.SMA-Solar.com).
2)
Depending on the configured country data set