Configuration
3.3
Parameter Description
READ_HALL_CAL_POINT_HI The calibration point high for Hall sensor.
READ_HALL_CAL_POINT_LO The calibration point high for Hall sensor.
ACTION_TYPE
Select the direct or reverse action: 0 = direct
1 = reverse
BACKUP_RESTORE
This parameter allows to save and to restore data according to factory and user calibration
procedures. It has the following options:
1, "Factory Cal Restore",
2, "Last Cal Restore",
3, "Default Data Restore",
4, "Shut-Down Data Restore",
5, "Sensor Data Restore",
11, "Factory Cal Backup",
12, "Last Cal Backup",
14, "Shut-Down Data Backup",
15, "Sensor Data Backup",
0, "None".
XD_ERROR
Indicates the condition of calibration process according to:
{16, "Default value set"},
{22, "Applied process out of range"},
{26, "Invalid configuration for request"},
{27, "Excess correction"},
{28, "Calibration failed"}
MAIN_BOARD_SN Main board serial number
EEPROM_FLAG
Indicate that the device is saving data in EEPROM memory: 0 = false
1 = true
ORDERING_CODE Indicates information about the sensor and control from production factory.
Table 3.1 - Transducer Block Parameter Description