-84-
No.PF※※-OMZ0002
Product individual parameters (continued)
Index
Sub
index
Access
1
Parameter
Data
type
2
Initial
value
Data
storage
3
Set value
4
Remarks
dec hex
1300
5
0x0514
1 R/W
OUT1 accumulated flow
setting
AC1_L
(Mantissa L)
U16 0 Y
Setting range
0 to 9999
Setting of OUT1 mantissa
Unit: when “L” is selected
2 R/W
AC1_L
(Index L)
U16 0 Y
Setting range
0 to 6
Setting of OUT1 index
Unit: when “L” is selected
1310
5
0x051E
1 R/W
AC1_L
(Mantissa Ft
3
)
U16 0 Y
Setting range
0 to 9999
Setting of OUT1 mantissa
Unit: when “Ft” is selected
2 R/W
AC1_L
(Index Ft
3
)
U16 0 Y
Setting range
0 to 6
Setting of OUT1 index
Unit: when “Ft” is selected
1410
0x0582
1 R/W
OUT2 setting
oUt2
(Selection output mode)
U8 0 Y
0: HYS (Hysteresis)
1: Wind
(Window comparator
)
2: AC
(Accumulated output
)
3: PLS
(Accumulated pulse
)
4: Err (Error output)
5: oFF (Output OFF)
Setting of OUT2 output mode
2 R/W
2ot
(Selection of output type)
U8 0 Y
0: 2_P (Normal output
)
1: 2_n (Reverse output
)
Setting of OUT2 output normal and
reserved output.
1420
0x058C
1 R/W
OUT2 switch point.
P_2 (n_2)
(Selection of output
set value)
S16
2000
Y
Setting range
-200 to 4200
Setting of OUT2 output set value
(Hysteresis)
2 R/W
H_2
(Setting of OUT2
hysteresis)
S16 200 Y
Setting range
0 to 4400
Setting of OUT2 hysteresis
(Hysteresis)
3 R/W
P2L (n2L)
(Lower limit of
window
comparator)
S16
1200
Y
Setting range
-200 to 4200
Setting of OUT2 output set value
(Lower limit of window comparator)
4 R/W
P2H (n2H)
(Upper limit of
window comparator)
S16
2400
Y
Setting range
-200 to 4200
Setting of OUT2 output set value
(Upper limit of window comparator)
5 R/W
WH2
(Window comparator
hysteresis)
S16 400 Y
Setting range
0 to 2200
Setting of OUT2 hysteresis
(Window comparator)
6 R/W
dtH2
(Delay time at ON)
S16 0 Y
Setting range
0 to 6000
Setting of OUT2 delay time at ON
10 ms increment
7 R/W
dtL2
(Delay time at OFF)
S16 0 Y
Setting of OUT2 delay time at OFF
10 ms increment
1500
5
0x05DC
1 R/W
OUT2 accumulated flow
setting
AC2_L
(Mantissa L)
U16 0 Y
Setting range
0 to 9999
Setting of OUT2 mantissa
Unit: when “L” is selected
2 R/W
AC2_L
(Index L)
U16 0 Y
Setting range
0 to 6
Setting of OUT2 index
Unit: when “L” is selected
1510
5
0x05E6
1 R/W
AC2_L
(Mantissa Ft
3
)
U16 0 Y
Setting range
0 to 9999
Setting of OUT2 mantissa
Unit: when “Ft” is selected
2 R/W
AC2_L
(Index Ft
3
)
U16 0 Y
Setting range
0 to 6
Setting of OUT2 index
Unit: when “Ft” is selected
1600
0x0640
0 R/W
AC
(Setting of the accumulated
flow output direction)
U8 0 Y
0: Add (Addition)
1: dEC1
(Subtraction OUT1)
2: dEC2
(Subtraction OUT2)
Setting of the accumulated flow
output direction
1030
0x0406
0 R/W
FiL
(Digital filter)
U8 3 Y
00.05 sec
10.1 sec
20.5 sec
31.0 sec
42.0 sec
55.0 sec
Setting of digital filter