-83-
No.PF※※-OMZ0002
Product individual parameters
Index
Sub
index
Access
1
Parameter
Data
type
2
Initial
value
Data
storage
3
Set value
4
Remarks
dec hex
1000
0x03E8
0 R/W
Unit
(Unit setting)
U8 0 Y
0: L (L/min)
1: Ft (cfm)
When the unit selection function is
not included,
a read/write to an un-selectable item
is rejected.
1010
0x03F2
0 R/W
CoL
(Selection of display colour)
U8 2 Y
0: rEd
(Constantly red)
1: Grn
(Constantly green)
2: 1SoG
(OUT1 turns green at ON)
3: 1Sor
(OUT1 turns red at ON)
4: 2SoG
(OUT2 turn
s green at ON)
5: 2Sor
(OUT2 turns green at ON)
Setting of display colour
1020
0x03FC
0 R/W
NorP
(Selection of switch output
PNP/NPN)
U8 1 Y
0: NPN
1: PNP
Setting of switch output specification
1030
0x0406
0 R/W
i_o
(select switch output/
external input)
U8 1 Y
0: oUt (switch output)
1: in (external input)
Setting OUT2 output specification
setting
1070
0x042E
0 R/W
rEF
(reference condition)
U8 1 Y
0: Std
(Standard condition)
1: PNP
(reference condition)
Measurement Units criteria setting
1210
0x04BA
1 R/W
OUT1 setting
oUt1
(Selection output mode)
U8 0 Y
0: HYS (Hysteresis)
1: Wind
(Window comparator
)
2: AC
(Accumulated output
)
3: PLS
(Accumulated pulse
)
4: Err (Error output)
5: oFF (Output OFF)
Setting of OUT1 output mode
2 R/W
1ot
(Selection of output type)
U8 0 Y
0: 1_P (Normal output
)
1: 1_n (Reverse output
)
Setting of OUT1 output normal and
reserved output.
1220
0x04C4
1 R/W
Set OUT1 switch point.
P_1(n_1)
(Selection of output
set value)
S16
2000
Y
Setting range
-200 to 4200
Setting of OUT1 output set value
(Hysteresis)
2 R/W
H_1
(Setting of OUT1
hysteresis)
S16 200 Y
Setting range
0 to 4400
Setting of OUT1 hysteresis
(Hysteresis)
3 R/W
P1L(n1L)
(Lower limit of
window
comparator)
S16
1200
Y
Setting range
-200 to 4200
Setting of OUT1 output set value
(Lower limit of window comparator)
4 R/W
P1H(n1H)
(Upper limit of
window comparator)
S16
2400
Y
Setting range
-200 to 4200
Setting of OUT1 output set value
(Upper limit of window comparator)
5 R/W
WH1
(Window comparator
hysteresis)
S16 400 Y
Setting range
0 to 2200
Setting of OUT1 hysteresis
(Window comparator)
6 R/W
dtH1
(Delay time at ON)
S16 0 Y
Setting range
0 to 6000
Setting of OUT1 delay time at ON
10 ms increment
7 R/W
dtL1
(Delay time at OFF)
S16 0 Y
Setting of OUT1 delay time at OFF
10 ms increment