-82-
No.PF※※-OMZ0002
●Device access lock parameter (index 12)
The contents are as follows.
Data type: 16 bit Record
0
Key lock release, DS unlock (Initial value)
Key lock release, DS lock
10
[Key lock]
This function prevents the user from physically changing the setting of the flow switch (button operation is
not accepted).
Even when key lock function is activated, settings can be changed by IO-Link communication.
Restoration by data storage (overwriting parameter data) can be performed.
[Lock data storage (DS lock)]
Locking "Data storage" will invalidate the data storage function of the flow switch.
In this case, access will be denied for backup and restoration of data storage.
●Device state parameters (index 36)
Readable device states are as follows.
Data type: 8 bit UInteger
0
1
Maintenance inspection required Not available
2
Outside specification range
Outside the flow measurement range
Below the flow measurement range
3
4
Internal failure of digital flow switch
●Device detail status parameters (index 37)
Detailed event contents of readable device status are as follows.
Array Event content
Event code
1
Internal failure of digital flow switch Error
0xF4 0x8D03
Internal failure of digital flow switch
3
Internal failure of digital flow switch
0xF4 0x8D05
4
Internal failure of digital flow switch
0xF4 0x8D01
Internal failure of digital flow switch
6
Internal failure of digital flow switch
0xF4 0x8D08
7
0xF4 0x8CC0
Outside the accumulated flow measurement
9
Outside the instantaneous flow measurement
0xF4 0x8C10
10
Below the instantaneous flow measurement
0xE4 0x8C30
11
Test event A warning
0xE4 0x8CA0
13
Data storage upload request
0x54 0xFF91