-81-
No.PF※※-OMZ0002
●ISDU parameters
Index
(dec)
Sub
index
Access
∗1
Parameters Initial value Remarks
0x0002
(2)
0 W
System command
-
Refer to "System command" on
page 81.
0x000C
(12)
0 R/W
Device access lock
0x0000
Refer to "Device access lock
parameter" on page 82.
0x0010
(16)
0 R
Vendor name
SMC Corporation
0x0011
(17)
0 R
Vendor text
www.smcworld.com
0x0012
(18)
0 R
Product name
Example:
PF2MC7xx-xx-Lx-xxx
0x0013
(19)
0 R
Product ID
Example:
PF2MC7xx-xx-Lx-xxx
0x0014
(20)
0 R
Product text
FloW sensor
0x0015
(21)
0 R
Serial number
Example:
"xxxxxxxx"
•Initial value is indicated as 8 digits.
•16 octets fixed character string
0x0016
(22)
0 R
Hardware version
HW-Vx.y
x: Large revision number
y: Small revision number
0x0017
(23)
0 R
Software version
FW-Vx.y
x: Large revision number
y: Small revision number
0x0024
(36)
0 R
Device status
parameter
-
Refer to "Device state parameters"
on page 82.
0x0025
(37)
0 R
Device detailed
state parameter
-
Refer to "Device detailed state
parameter" on page 82.
0x0028
(40)
0 R
Process data input
-
The latest value of process data
can be read.
∗1: R: Read, W: Wright
●System command (index 2)
In the ISDU index 0x002 SystemCommand (system command), the command shown in the table below
will be issued.
The button of each system command is displayed on the IO-Link setting tool (excluding
"ParamDownloadStore").
Click the button to send the system command to the product.
Writable commands are shown below.
Data type: 8 bit UInteger
129
Application Reset
Reset of the peak/bottom value (flow/temperature)
Reset of the accumulated flow value
130
Initialize the set value to the default value.
170
Reset of peak / bottom value (flow rate)
190
Reset of the accumulated flow value