ASYS
16 A Transfer System
ENGLISH
IOMASY160810-GB_00
15
TR O U b l E S H O O T I N G8.
If problems should occur, please check the following points before contacting the
customer service department:
Is the mains voltage present at the ASYS TRANSFER SWITCH input?
Has one of the two input fuses tripped or open?
If you contact the customer service department, please have the following informa-
tion ready:
Device information (model name and serial number)
An exact description of the problem (what load is being supplied, does the prob-
lem occur regularly or sporadically, ...)
Rectication of errors
Problem Possible Cause Solution
No display, no alarm. Mains or feeding UPS
units switched o.
Switch on the mains or feeding
UPS units.
No mains voltage
present.
Have mains inspected by qualied
electrician.
Input fuses tripped. Check and make sure the load ca-
pacity is within the specication,
then replace a good fuse. If the
problem persists, contact the cus-
tomer service department.
Both mains indicator
S1 and S2 do not il-
luminate, when mains
voltage present.
Both input fuses
tripped.
Check and make sure the load ca-
pacity is within the specication,
then replace a good fuse. If the
problem persists, contact the cus-
tomer service department.
Alarm indicator F1 il-
luminates, acoustic
alarm active with 0.5
second sequence.
ASYS Fault. Contact the customer service de-
partment.
Multiples consecutive
transfers detection
Check the quality of the preferred
source
Overheating Check and make sure the load ca-
pacity is within the specication,
or decrease ambient temperature
(less than 40°C).