- 27
-
30071
Frequency of supply voltages.
4 Float Hz 00 46
30073
Total Import kWh
4 Float kWh 00 48
30075
Total Export kWh.
4 Float kWH 00 4A
30077
Total Import kVArh .
4 Float kVArh 00 4C
30079
Total Export kVArh .
4 Float kVArh 00 4E
30081
Total VAh
4 Float kVAh 00 50
30083
Ah
4 Float Ah 00 52
30085
Total system power demand (2).
4 Float W 00 54
30087
Maximum total system power demand
(2).
4 Float W 00 56
30101
Total system VA demand.
4 Float VA 00 64
30103
Maximum total system VA demand.
4 Float VA 00 66
30105
Neutral current demand.
4 Float Amps 00 68 X X
30107
Maximum neutral current demand.
4 Float Amps 00 6A X X
30109
Total system reactive power demand. (2)
4 Float VAr 00 6C X
30111
Maximum total system reactive power
demand(2)
4 Float VAr 00 6E X
30201
Line 1 to Line 2 volts.
4 Float V 00 C8 X
30203
Line 2 to Line 3 volts.
4 Float V 00 CA X
30205
Line 3 to Line 1 volts.
4 Float V 00 CC X