- 30
-
30377
L1 total kvarh (3)
4 Float kVArh 01 78
30379
L2 total kvarh (3)
4 Float kVArh 01 7A X
30381
L3 total kvarh (3)
4 Float kVArh 01 7C X
30385
resettable total active energy
4 Float kWh 01 80
30387
resettable total reactive energy
4 Float kVArh 01 82
30389
resettable import active energy
4 Float kWh 01 84
30391
resettable export active energy
4 Float kWh 01 86
30393
resettable import reactive energy
4 Float kVArh 01 88
30395
resettable export reactive energy
4 Float kVArh 01 8A
Function code
10 to set holding parameter
03 to read holding parameter
Address
Register
Parameter
Number
Parameter
Modbus
Protocol
Start Address
Hex
Valid range
Mode
High
Byte
Low
Byte
40003 2
Demand
Period
00 02
Write demand period: 0, 5,8, 10,
15, 20, 30 or 60 minutes, default 60.
Setting the period to 0 will cause the
r/w