- 31
demand to show the
Current parameter value and demand
max to show the maximum parameter
value since last demand reset.
Length : 4 byte
Data Format : Float
40011 6 System Type 00 0A
Write system type: 3p4w = 3, 3p3w = 2 &
1p2w= 1
Requires password, see parameter 13
Length : 4 byte
Data Format : Float
r/w
40013 7 Pulse1 Width
00 OC
Write pulse1 on period in milliseconds:
60, 100 or 200, default 100.
Length : 4 byte
Data Format : Float
r/w
40015 8 Password Lock
00 OE
Write any value to password lock
protected registers.
Read password lock status:
0 = locked. 1 = unlocked.
Reading will also reset the password
timeout back to one minute.
Length : 4 byte
Data Format : Float
r
40019 10
Stop
00 12
Write the network port parity/stop bits
for MODBUS Protocol, where: 0 = One
stop bit and no parity, default. 1 = One
stop bit and even parity. 2 = One stop bit
r/w