17EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
6.8 Module summary table, starting from 0x0036
MODBUS makes it possible to view the module status from the Unit level through following table:
MODULYS GP STATUS
Unit address Bits Acronym Description
0x1036
b00 S096 Module 1 Operating
MODULES
b01 S097 Module 2 Operating
b02 S098 Module 3 Operating
b03 S099 Module 4 Operating
b04 S100 Module 5 Operating
b05 S101 Module 6 Operating
b06 S102 Module 7 Operating
b07 S103 Module 8 Operating
b08 S104
b09 S105
b10 S106
b11 S107
b12 S108
b13 S109 Bypass Operating
b14 S110
b15 S111
0x1037
b00 S112 1 Available
MODULES
b01 S113 2 Available
b02 S114 3 Available
b03 S115 4 Available
b04 S116 5 Available
b05 S117 6 Available
b06 S118 7 Available
b07 S119 8 Available
b08 S120
b09 S121
b10 S122
b11 S123
b12 S124
b13 S125 Bypass Available
b14 S126
b15 S127