MASTERYS IP+
40-60 kVA 3/1
ITALIANOENGLISH
10
IOMMASIPXX07-GB 02
free area
UNPACKING AND INSTALLATION
OF THE UNIT
3
3.3 ENVIRONMENTAL REQUISITES.
The recommended operating temperature, humidity and altitude values are listed in the technical speci cations
table (see chapter 11). Cooling systems may be required to maintain these values.
Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or
chemical solutions).
The UPS is not designed for outdoor use.
Do not expose the UPS to direct sunlight or to sources of excessive heat.
A space of at least 40 cm must be left at the back for adequate ventilation (see  gure 3.3-1).
The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the front of
the UPS for maintenance purposes. It is also recommended to ensure that the cable connections are su ciently
long and  exible to allow easy maintenance operations (see  gure 3.3-1).
If it is not possible to leave su cient space at the front, adequate access must be ensured from both sides.
3.3-1
40 cm
1,5 m
20 cm20 cm
MASTERYS
UPS
WARNING!
This is a product for commercial and industrial application in the second environment – installation
restrictions or additional measures may be needed to prevent disturbances.

Questions and Answers: