MASTERYS IP+
40-60 kVA 3/1
ENGLISH
IOMMASIPXX07-GB 02
47
10
PROBLEM SOLVING
A38, A39, A40, A41: external alarm 1, 2, 3, 4.
One of the ADC PCB inputs has been activated; check the situation of the devices connected to this PCB.
A56, A57: generator general alarm.
The generator has sent an alarm; check directly on the GE.
A61: wrong phase cycle direction.
The phase cycle sequence is incorrect. In this case, invert two phases of the input mains. For a UPS with sepa-
rate auxiliary mains, exchange the two phases of the auxiliary mains only.
10.2 UPS ALARMS.
A01: battery alarm.
Failure or problem on the battery circuit. Check that the battery switch is closed.
A18: inverter blocked due to overload.
Reduce the load rate applied to the UPS and reset the alarms.
A20: wrong con guration.
Error in the con guration parameters; please contact the support service.
A30: block due to overload.
Reduce the load rate applied to the UPS and reset the alarms.
A42: T.Service general alarm.
The MASTERYS™ products can be remotely serviced. This alarm indicates that a procedure for analysing the
UPS failure has been activated by the support centre (if an e-service contract has been concluded).
A44: programmed control.
The equipment has to undergo periodic checks by the support service in order to ensure optimum perform-
ance and e ciency. If the “Programmed Control” signal appears on the mimic panel, the equipment should
be inspected by an adequately trained technician.
A47: maximum battery temperature.
The temperature of the battery cabinet (or of the battery room) is higher than the maximum allowed. Check
the ventilation or air conditioning system in the premises.
A59: battery circuit open.
Battery switch open.
A60: fan failure.
Fault in the ventilation system; check that the air inlet at the front and the air outlet of the UPS are not ob-