MASTERYS IP+
40-60 kVA 3/1
ITALIANOENGLISH
6
IOMMASIPXX07-GB 02
2.1 IMPORTANT.
• This document provides important instructions for the safe use, movement and connection of the MASTERYS™ un-
interruptible power system (UPS).
• SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize
the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All
reproduction, modi cation, dissemination of this document whether in part or whole and by any manner are
expressly prohibited except upon Socomec’s express prior written consent.
• This document is not a speci cation. SOCOMEC UPS reserves the right to make any changes to data without prior
notice.
• The unit must be installed and activated only by quali ed technical personnel and authorised by SOCOMEC UPS.
The UPS MUST only be moved by two people at least bt the mean of a forklift.
• The unit must remain in a vertical position in all circumstances.
• Connect the PE ground conductor  rst before you make any other connection.
• Do not expose the UPS to rain or liquids in general. Do not introduce external bodies.
• If the UPS is not equipped with automatic sectioning against back feed or if the switch is external to the UPS, a x
a label bearing the following words on all the external switches of the UPS power supply:
• Keep this manual handy for future consultation.
• If the unit fails, it must be repaired only by authorised technicians that have been specially trained for this pur-
pose.
• This equipment conforms to the European Community directives for professional equipment and bears the ap-
proval mark
• The UPS requires three-phase plus neutral input connections (3P+N).
• The output neutral of the transformer is not connected to the ground. The internal isolation transformer modi es
the neutral arrangements of the system.
WARNING!
The output neutral of the transformer is not connected to the ground.
• Before connecting any external battery cabinet, ensure that it is fully compatible with the model of UPS it is to be
used with.
• The use of external battery cabinets not supplied by the manufacturers is not recommended.
SAFETY