MASTERYS IP+
40-60 kVA 3/1
ENGLISH
IOMMASIPXX07-GB 02
41
COMMUNICATION
9
Password: allows the user to
change the password to access
the html. To authorise access only
to users that have a password. In-
sert the new password and write
it down in case of need.
JBUS TCP/IP Port: used to accept
a JBUS frame through LAN tunnel-
ling .
Client JBUS IP address to be au-
thorised: if a speci c IP address is
inserted in this box, then only that
address/user will be able to ac-
cess the html pages. If the address
0.0.0.0 is used, all the PCs on the
network will be able to access the
supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all users.
Software updating: if on, allows the supervisor to be updated.
Page refresh (sec): the page refresh rate can be set.
Installation: text string used to describe the UPS installation site, which is useful if there are more than one
unit connected (this value is inserted in SMS messages or e-mails).
NTP Server: indicates the IP address of the time server to automatically update the date and time on the system.
GMT Correction (minutes): indicates local time and the o set in minutes with respect to the zero meridian of
Greenwich
Apply the parameter settings: restarts the monitoring system with the new settings.