NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
93
EN
10.3.8. Operation Procedures
1. Follow Chapter 10.3.6: Connection to connect the UPS and the lithium-ion battery
pack.
2. After making sure that the UPS and the lithium-ion battery pack have been rmly
connected with the provided battery cable and RS-485 cable, turn on the lithium-
ion battery pack’s breaker and the UPS’s input breaker.
3. Follow the NETYS RT Series UPS’s User Manual to turn on the UPS.
After usage, you can turn off the lithium-ion battery pack safely by following
the steps below:
Step : Turn off the lithium-ion battery pack’s breaker.
Step : Disconnect the provided RS-485 cable.
Step : Disconnect the provided battery cable.
10.3.9. Maintenance
It is recommended that you follow the following maintenance items and intervals to
ensure the reliability and efciency of the lithium-ion battery pack.
1. Check the State of Capacity every week via the LCD on the UPS.
2. Check the State of Health (SOH) every 3 months (i.e. perform a deep discharge
test). If the SOH is lower than 30%, please replace the lithium-ion battery module.
3. Check the air ow every month.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec NRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA and is the answer not in the manual?

socomec NRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA Specifications

General IconGeneral
Brandsocomec
ModelNRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA
CategoryUPS
LanguageEnglish

Related product manuals