EasyManuals Logo

socomec NRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA User Manual

socomec NRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
94
EN
10.3.10. Technical Specications
Battery Type NMC
Battery Module Rated Capacity 4.4 Ah
Max. Discharging Power
1 battery module: 11kW
2 battery modules: 22kW
Nominal Voltage 189 Vdc
Nominal Current 60A
Connection Battery connector
Breaker 63A, ± 250 Vdc 3P
Charging
Max. Charging Voltage 216 Vdc
Max. Charging Current 5.7A
Communication Interfaces RJ45 (RS-485) Port x1
Physical
Dimensions
(W x D x H )
External battery pack:
440 x 646 x 89 mm
(17.3” x 25.5” x 3.5”)
Battery module:
212 x 506 x 76.8 mm
(8.3” x 19.9” x 3.0”)
Weight
External battery pack with 2 battery
modules: 37.7 kg (83 lb)
External battery pack with 1 battery
module: 12.0 kg (26.5 lb)
Environ-
ment
Operating Altitude
0 ~ 3000 m (0 ~ 10000 ft);
0 ~ 1000 m (0 ~ 3300 ft)
(without derating)
Operating Temperature 0°C ~ 45°C (32°F ~ 113°F)
Storage Temperature -15°C ~ 50°C (-59°F ~122°F)
Relative Humidity 5% ~ 95% (non-condensing)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec NRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA and is the answer not in the manual?

socomec NRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA Specifications

General IconGeneral
Brandsocomec
ModelNRT3-U5000 & NRT3-U5000C & NRT3-U7000 & NRT3-U7000C & NRT3-U7000CLA
CategoryUPS
LanguageEnglish

Related product manuals