SOFAR 15~24KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 56 -
ID100
Reserved
Reserved
There are internal faults of inverter, turn
OFF the DC switch, wait for 5 minutes,
then turn ON the DC switch. Check
whether the fault is rectified. If no, please
contact technical support.
ID102
HwPVOCP
PV hardware
overcurrent
ID103
HwACOCP
AC output
hardware
overcurrent
ID110
Overload1
Overload
Protection 1
ID111
Overload2
Overload
Protection 2
ID112
Overload3
Overload
Protection 3
ID113
OverTempD
erating
Overtemperat
ure derating
Ensure the installation position and
installation method meet the requirements
of this user manual.
Check whether the ambient temperature
of the installation position exceeds the
upper limit. If yes, improve ventilation to
decrease the temperature.
Check whether the inverter has dust and
dust, whether there are foreign matters
blocking the fan at the air inlet. If so, please
improve the ventilation and heat
dissipation of the environment. It is
recommended that the inverter should be
cleaned once every half a year.