SOFAR 15~24KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 57 -
ID114
FreqDeratin
g
Frequency
derating
If it occurs frequently, please check
whether the grid voltage and grid
frequency are within the allowable range
of the inverter; if not, please contact the
customer service of SOFARSOLAR; if yes,
please check whether the connection
between the circuit breaker at the AC side
and the output cable is normal; if the grid
voltage and grid frequency are within the
allowable range of the inverter, and the AC
side wiring is confirmed to be correct, the
alarm still appears frequently With the
approval of the local power operator,
please contact the customer service of new
energy of Capital Airlines to modify the
protection points of over / under voltage
and over / under frequency of inverter grid.
ID115
FreqLoading
Frequency
loading
ID116
VoltDerating
Voltage
derating
ID117
VoltLoading
Volatge
loading
ID124
Reserved
Reserved
There are internal faults of inverter, turn
OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check
whether the fault is rectified. If no, please
contact technical support.
ID125
Reserved
Reserved
ID129
unrecoverH
wAcOCP
Output
overcurrent
hardwareper
manent fault
ID130
unrecoverBu
sOVP
Busovervoltag
epermanent
fault