Chapter 6: LCD – Status Screens and Setup Options
Firefighter Gateway Installation Guide MAN-01-00113-1.2
29
Setup Menu Options
This section describes basic gateway configuration options.
1 Verify that the SolarEdge gateway is connected to a power outlet.
2 Press the Enter button until the following message is displayed:
P l e a s e ente r
P a s s w o r d
* * * * * * * *
The gateway is now in Setup mode and all its LEDs are lit. The gateway automatically exits Setup
mode if no buttons are pressed for more than 2 minutes.
3 Use the three-right-most LCD buttons to type in the following password: 12312312. The following
message is displayed:
L a n g u a g e < e n g >
C o m m u n i c a t i o n
R e m o t e S h u t d o w n
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n