Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional)
Firefighter Gateway Installation Guide MAN-01-00113-1.2
37
Set IP: Enables setting the IP of the gateway according to the LAN settings:
Use the Up and Down buttons to adjust the value of each IP address octet.
Press the Enter button to move to the next IP address octet.
Long press the Enter button (until Applied message appears) apply the value
Long press the Esc button (until Aborted message appears) erase all characters
S e t u p I P
1 9 2 . 1 6 8 . 2 . 7
Set Mask: Set the subnet mask of the SolarEdge gateway according to the LAN settings.
Set Gateway: Set the gateway address of the SolarEdge gateway according to the LAN settings.
Set DNS: Set the DNS of the SolarEdge gateway according to the LAN settings.
Set Server Addr: Set the IP address of the SolarEdge monitoring portal. This option is predefined in
the SolarEdge gateway to specify the SolarEdge monitoring portal IP address and does not normally
need configuration.
Set Server Port: Set the port through which to connect to the SolarEdge monitoring portal. This
option is predefined in the gateway to specify the SolarEdge monitoring portal IP port and normally
does not need configuration.
NOTE:
If your LAN has a firewall, you must verify that the address and port configured in the Set Server
Addr and the Set Server Port fields are not blocked.
You may need to configure it to enable the connection to the following address:
Destination Address: prod.solaredge.com
Port: 22222
Connecting and Configuring LAN
To connect the Ethernet port to the router/switch:
1 Use a pre-crimped cable or use a crimper to prepare an RJ45 communication connector on both ends
of a standard CAT5/6 cable: Insert the eight wires into the RJ45 connector.
CAT5/6 standard cables have eight wires (four twisted pairs), as shown in the diagram below. Wire
colors may differ from one cable to another. You can use either wiring standard, as long as both sides
of the cable have the same pin-out and color-coding.
RJ45 Pin #
Wire Color
3
10Base-T Signal
100Base-TX Signal
T568B
T568A
1
White/Orange
White/Green
Transmit+
2
Orange
Green
Transmit-
3
White/Green
White/Orange
Receive+
4
Blue
Blue
Reserved
5
White/Blue
White/Blue
Reserved
6
Green
Orange
Received-
7
White/Brown
White/Brown
Reserved
8
Brown
Brown
Reserved
3
The firefighter gateway connection has a 568A layout and does not support RX/TX polarity change. Supporting crossover
Ethernet cables depends on the switch capabilities.