64
L30US-IB80, L30US-IB00, L40US UPS
Model L30US-IB80 L30US-IB00 L40US
Voltage window (At 100%/50%
load)
-20%, +25% (166-260Vac ), Full load
-40%, +25% (125-260Vac ), <50% Load
Backfeed contact point Dry contact: 24VDC/250mA
Dual feed Standard with busbar configuration as single feed
Nominal Input rate current(A) 89A 119A
Max Input current(A) 113A 150A
Battery
Battery types VRLA
Build-in battery
80pcs 9Ah NA
±120VDC
NA
Battery block flexibility
Optional Voltage: ±96/108/120/132/144/156VDC
(16/18/20/22/24/26PCS OPTIONAL) 192VDC312VDC
(16~26pcs, 20 pcs define, 20~26pcs no power
derating; 18pcs output power factor 0.9; 16pcs output
power factor 0.8;)
Charge capacity 20A Max. 40A Max.
Battery temperature
compensation (standard /
optional)
0 -7 millivolts per cell for every Fahrenheit degree, starting
from 82.4°F
Battery test
Manually and automatically programmable by time or
voltage
Decentralized battery in parallel
mode
Support
Output
Overload
Online mode 110% 60mins, 125% 10mins, 150% 1mins
Battery mode 110% 60mins, 125% 10mins, 150% 1mins
THDU Linear load 2%