L30US-IB80, L30US-IB00, L40US UPS
Model L30US-IB80 L30US-IB00 L40US
Non-linear
load
5%
Output PF 1
Output voltage 208Vac(3Ph+N+PE)
Slew rate -Maximum frequency
variation
0.5~2Hz/s
Bypass source voltage
windows setup and Frequency
windows setup
Frequency±10%±5%, ±4%, ±2%, ±1%
Upper limit: +10, +15, +20 or 25% (default: +20)
Lower limit: -10, -20, -30 or -40 (default: -30)
Output voltage compensation
(support downstream
transformer)
-5%~+5%
Output rate current 83A 111A
System features
Cooling
Cooling type
(heat pipe,
liquid, air)
Air
Air flow input
/ output
Air inlet: front
Air outlet: rear
Internal Breaker
Internal
mains
125A 3P 150A 3P
Internal
bypass
125A 3P
Internal
maintenance
bypass
125A 3P
Internal
output
125A 3P