Ø Advance settings
Setting
Setting
Safety Code
Grid Parameters
Advanced
>
a) Safety Code
User can set safety standard according to different countries and grid tied.
There are now several standards to choose from. (There may be changes in
Item
1
Country
ARN 4105
Standard
German
OverVoltage_L1
UnderFreq_L1
UnderVoltage_L1
Vac 10min Avg
OverVoltage_L2
OverFreq_L2
UnderVoltage_L2
OverFreq_L1
UnderFreq_L2
Tovp_L1
Tuvp_L1
Tovp_L2
Tofp_L1
Tuvp_L2
Grid Parameters
Tofp_L2
Reconnection Time
Tufp_Fast
Checking Time
OFPL_Setting
W(Gra)
UFPL_Setting
Local Command
Grid Parameters
92
93
Advanced settings
a)
b)
c)
d)
e)
f )
g)
h)
i)
j)
k)
l)
m)
n)
o)
p)
q)
r)
s)
t)
u)
v)
w)
Safety Code
Meter/CT Settings
Grid Parameters
Self Test
FVRT Function
Shadow Fix
Pu Function
Modbus
Export Control
Power Factor
Advance Password
DRM Function
Reset
Power Limit
Main Breaker Limit
Battery Heating
EPS Setting
Charger
External ATS
Parallel Setting
ShutDown
MicroGrid
PV Connection
x)
AS4777 Setting
ExternalGen
y)
OverVoltage_L1
UnderFreq_L1
UnderVoltage_L1
Vac 10min Avg
OverVoltage_L2
OverFreq_L2
UnderVoltage_L2
OverFreq_L1
UnderFreq_L2
UnderFreq_L2
Tovp_L1
Tuvp_L1
Tovp_L2
Tofp_L1
OverFreq_L2
Tuvp_L2
Grid Parameters
Tofp_L2
Reconnection Time
Tufp_Fast
Checking Time
OFPL_StartPoint
OFPL_SetRate
OFPL_DelayTime
W(Gra)
UFPL_StartPoint
UFPL_SetRate
UFPL_DelayTime
Grid Parameters
Tufp_L1
All advanced settings can be set here, such as battery, grid, EPS(Off-grid), etc..
"Advanced" setting is generally customization and resetting for battery and
grid. Each part has lower level parts.
Please contact your installer or factory and enter the installer password.
.
>Safety
Country
>AS4777_2020_A<
Enter
Back
Up
Down
Up
Down
Country
>AS4777_2020_B<
Country
>AS4777_2020_A<
Country
>AS4777_2020_C<
**Previous page
Up
Down
Country
>New Zealand<
☆
SolaX will grant the setting permissions to its installers and
distributors.
Region Australia A Australia B Australia C New Zealand
AS4777_2020_A AS4777_2020_B AS4777_2020_C New Zealand
OV-G-V 265V 265V 265V 265V 230-300V
OV-G-V2 275V 275V 275V 275V 1-2S
OV-GV2-T 0.1S 0.1S 0.1S 0.1S 230-300V
UN-G-V1 180V 180V 180V 180V 0-0.2S
UNGV1-T 10S 10S 10S 10S 40-230V
UN-G-V2 70V 70V 70V 70V 10-11S
UNGV2-T 1.5S 1.5S 1.5S 1.5S 40-230V
OV-G-F1 52HZ 52HZ 55HZ 55HZ 1-2S
OVGF1-T 0.1S 0.1S 0.1S 0.1S 50-55HZ
OV-G-F2 52HZ 52HZ 55HZ 55HZ 0-0.2S
OVGF2-T 0.1S 0.1S 0.1S 0.1S 50-55HZ
OV-GV1-T 1.5S 1.5S 1.5S 1.5S 0-0.2S
UN-G-F1 47HZ 47HZ 45HZ 45HZ 45-50HZ
UNGF1-T 1.5S 1.5S 5S 1.5S 1-6S
UN-G-F2 47HZ 47HZ 45HZ 45HZ 45-50HZ
UNGF2-T 1.5S 1.5S 5S 1.5S 1-6S
Startup-T 60S 60S 60S 60S 15-1000S
Restore-T 60S 60S 60S 60S 15-600S
Recover-VH 253V 253V 253V 253V
Recover-VL 205V 205V 205V 198V
Recover-FH 50.15Hz 50.15Hz 50.15Hz 50.15Hz
Recover-FL 47.5Hz 47.5Hz 47.5Hz 47.5Hz
Start-VH 253V 253V 253V 253V
Start-VL 205V 205V 205V 198V
Start-FH 50.15Hz 50.15Hz 50.15Hz 50.15Hz
Start-FL 47.5Hz 47.5Hz 47.5Hz 47.5Hz