Operation Method Operation Method
Ø Menu interface
The menu interface (Level 2) is a transfer interface for the user to get into
other interface to finish the setting or get the information.
-User can get into this interface by long pressing “Down button when LCD
displays the main interface.
-User can select by moving the cursor with function button, and long press
“Down to confirm.
Ÿ Status
The status function contains two aspects, the grid and the solar.
Press ”Up“ and “Down” to select and long press down to confirm the
selection, long press “Up to return to Menu.
a) Grid
This status shows the current condition of the AC output port of the
inverter, such as voltage, current, output power and grid power. “Pout”
measures the output of the inverter, “Pgrid” measures power export to or
import from the grid. Positive value means the power feeds into the grid,
negative value means the power used from the grid.
Press ”Up“ and “Down button to review the parameter, long press “up” to
return to Status .
Power
0W
Normal
Status
Language
Grid
Solar
Status
Menu
Ø LCD Digital Display
The main interface (Level 1) is the default interface, the inverter will
automatically jump to this interface when the system started up successfully
or not operated for a period of time.
The interface shows the following information. “Power” means the timely
output power; “Pgrid” means the power export to or import from the grid;
(Positive value means the energy feeds into the grid, negative value means
the energy used from the grid); “Today means the power generated within
the day; Total” means the power generated until now.
Press ”Up“ and “Down” to review the information.
> O/V Stage2
Up
Down
Up
Down
> U/V Stage2
> U/V Stage3
Up
Down
287.5
> O/V Stage3
287.5
103.5
103.5
Up
Down
>Enable<
> Freq ROCOF
> T_Start
Up
Down
Up
Down
Up
Down
60s
> H/LVRT Function
Disable
Up
Down
> Qu_3Tau
10.0s
> Pu_3Tau
10.0s
>VacOvp1stTime
> O/F Stage1
51.50
> U/F Stage1
Up
Down
47.50
> U/F Stage2
Up
Down
47.50
> O/F Stage2
Up
Down
51.50
Up
Down
Up
Down
Up
Down
> Frt_EntryVoltUp
266.8
> Frt_EntryVoltDn
181.8
0.10s
Up
Down
>VacOvp2ndTime
0.10s
Up
Down
253.0
> O/V 10min set
> O/V 10min En
>Disable<
Up
Down
Up
Down
>FacUfp1stTime
>FacUfp2ndTime
Up
Down
0.10s
0.10s
>VacUvp1stTime
>VacUvp2ndTime
Up
Down
>FacOfp1stTime
Up
Down
>FacOfp2ndTime
Up
Down
Up
Down
3.00s
0.30s
0.10s
0.10s
Up
Down
>ReConnectTime
60s
Up
Down
>CosP_3Tau
3s
Up
Down
42 43

Other manuals for SolaX Power X3-MIC G2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolaX Power X3-MIC G2 Series and is the answer not in the manual?

SolaX Power X3-MIC G2 Series Specifications

General IconGeneral
BrandSolaX Power
ModelX3-MIC G2 Series
CategoryInverter
LanguageEnglish

Related product manuals