EasyManua.ls Logo

Sourcetronic ST600 Series - Page 102

Sourcetronic ST600 Series
390 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-95-
27
Set value 2 of
EtherCAT/PROFITNET/Ethernet IP
communication
0–1000
28
AO1 from the Programmable card
0–1000
29
AO2 from the Programmable card
0–1000
30
Running speed
0–Twice the motor rated synchronous
speed.
31
Output torque (bipolar)
0–Twice the motor rated torque. A
negative value corresponds to 0.0% by
default.
32
AI/AO temperature detection output
AO value of AI/AO temperature detection
3347
Reserved
/
Related parameter list:
Function
code
Name
Description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse output
1: Open collector output
0
P06.14
AO1 output selection
0: Running frequency (0–Max. output
frequency)
1: Set frequency (0–Max. output frequency)
2: Ramp reference frequency (0–Max.
output frequency)
3: Rotational speed (0–Speed corresponding
to max. output frequency)
4: Output current (0–Twice the VFD rated
current)
5: Output current (0–Twice the motor rated
current)
6: Output voltage (0–1.5 times the VFD
rated voltage)
7: Output power (0–Twice the motor rated
power)
8: Set torque (0–Twice the motor rated
current)
9: Output torque (Absolute value, 0–+/-
Twice the motor rated torque)
10: AI1 input (0–10V/0–20mA)
11: AI2 input (0–10V)
12: AI3 input (0–10V/0–20mA)
13: HDIA input(0.00–50.00kHz)
14: Value 1 set through Modbus/Modbus
TCP (0–1000)
15: Value 2 set through Modbus/Modbus
TCP (0–1000)
0
P06.15
Reserved
0
P06.16
HDO high-speed pulse output
0

Table of Contents