Frequency Inverter ST600 High-Performance Multifunction Series VFD Optional peripheral
accessories
-363-
Note: The insulation resistance is reduced if it is damp inside the motor. If it may be damp, you need
to dry the motor and then measure the insulation resistance again.
D.5 Breaker and electromagnetic contactor
You need to add a fuse to prevent overload.
You need to configure a manually manipulated molded case circuit breaker (MCCB) between the AC
power supply and VFD. The breaker must be locked in the open state to facilitate installation and
inspection. The capacity of the breaker needs to be 1.5 to 2 times the VFD rated input current.
According to the working principle and structure of breakers, if the manufacturer's regulation
is not followed, hot ionized gases may escape from the breaker enclosure when short-circuit
occurs. To ensure safe use, exercise extra caution when installing and placing the breaker.
Follow the manufacturer's instructions.
To ensure safety, you can configure an electromagnetic contactor on the input side to control the
switch-on and switch-off of the main circuit power, so that the input power supply of the VFD can be
effectively cut off when a system fault occurs.
Table D-3 Parameters of the optional accessories for standard and SP model VFDs
Product model
Breaker rated current
(A)
Fast-acting fuse
rated current (A)
Contactor rated
current (A)
ST600-1R5G3
6
10
9
ST600-2R2G3
10
10
9
ST600/ST600SP-004G3
20
20
18
ST600/ST600SP-5R5G3
25
35
25
ST600/ST600SP-7R5G3
32
40
32
ST600/ST600SP-011G3
50
50
38
ST600/ST600SP-015G3
63
60
50
ST600/ST600SP-018G3
63
70
65
ST600/ST600SP-022G3
80
90
80
ST600/ST600SP-030G3
100
125
80
ST600/ST600SP-037G3
125
125
98
ST600/ST600SP-045G3
140
150
115
ST600/ST600SP-055G3
180
200
150
ST600/ST600SP-075G3
225
250
185

Table of Contents