EasyManua.ls Logo

Sourcetronic ST600 Series - P20-Encoder of Motor 1

Sourcetronic ST600 Series
390 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-217-
monitoring variable
2
P19.19
Ethernet
monitoring variable
3
0–65535
0
P19.20
Ethernet
monitoring variable
4
0–65535
0
P19.21
AI/AO detected
temperature
-20.0–200.0°C
0.0°C
P20––Encoder of motor 1
Function
code
Name
Description
Default
value
Modify
P20.00
Encoder type
display
0: Incremental encoder
1: Resolver-type encoder
2: Sin/Cos encoder
3: Endat absolute encoder
0
P20.01
Encoder pulse
number
Number of pulses generated when the encoder revolves
for one circle.
Setting range: 0–60000
1024
P20.02
Encoder direction
0x000–0x111
Ones: AB direction
0: Forward
1: Reverse
Tens: Z pulse direction (reserved)
0: Forward
1: Reverse
Hundreds: CD/UVW pole signal direction
0: Forward
1: Reverse
0x000
P20.03
Detection time of
encoder offline
fault
0.010.0s
2.0s
P20.04
Detection time of
encoder reversal
fault
0.0100.0s
0.8s
P20.05
Filter times of
encoder detection
Setting range: 0x00–0x99
Ones: Low-speed filter time, corresponds to 2^(0–
9)×125μs.
Tens: High-speed filter times, corresponds to 2^(0–
9)×125μs.
0x33
P20.06
Speed ratio
between encoder
mounting shaft
and motor
Users need to set this parameter when the encoder is
not installed on the motor shaft and the drive ratio is not
1.
Setting range: 0.001–65.535
1.000