Frequency Inverter ST600 Series High-Performance Multifunction VFD Installation Guide
-26-
4.3 Standard wiring of main circuit
4.3.1 Wiring diagram of main circuit
Figure 4-13 Main circuit wiring diagram of standard model VFDs
Note:
1. The fuse, DC reactor, braking unit, braking resistor, input reactor, input filter, output reactor and
output filter are optional parts. See Appendix D Optional peripheral accessories.
2. P1 and (+) have been short connected by default for standard model VFDs 132G3 and higher.
If you need to connect to external DC reactor, take off the short-contact tag of P1 and (+).
3. When connecting the braking resistor, take off the yellow warning sign marked with PB, (+) and
(-) on the terminal block before connecting the braking resistor wire, otherwise, poor contact may
occur.
4. Braking units are optional parts for standard model VFDs 045G3 and above.
037G3 and lower
models
045G3 - 110G3
models
132G3 and higher
models
Braking resistor
Braking unit
Braking resistor
Braking resistor
Braking unit
Input
reactor
Input
filter
Fuse
Input
reactor
Input
filter
3PH power
380V(-15%)-440V(+10%)
50/60Hz
R
S
T
R
S
T
U
V
W
PE
U
V
W
PE
Output
reactor
Output
filter
M
+ -
P1
+ -
PB
Fuse
Fuse
Input
reactor
Input
filter
R
S
T
U
V
W
PE
Output
reactor
Output
filter
Output
reactor
Output
filter
M
M
+ -
DC+
DC-
DC+
DC-
DC reactor
3PH power
380V(-15%)-440V(+10%)
50/60Hz
3PH power
380V(-15%)-440V(+10%)
50/60Hz