Note:
1. The rated input voltage drop of input reactors is 2%±15%.
2. The current adjustment coefficient on the input side of the VFD is higher than 90% after a DC reactor
is configured.
3. The rated output voltage drop of output reactors is 1%±15%.
4. The preceding tables describe external accessories. You need to specify the ones you choose when
purchasing accessories.
D.7 Filters
J10 is not connected in factory for standard model VFD 110G3 and lower. Connect the J10 packaged
with the manual if the requirements of level C3 need to be met;
J10 is connected in factory for standard model VFDs 132G3 and higher, all of which meet the
requirements of level C3.
The product is shipped with J10 jumper as standard on all SP models.
Note: Disconnect J10 in the following situations:
1. The EMC filter is applicable to the neutral-grounded grid system. If it is used for the IT grid system
(that is, non-neutral grounded grid system), disconnect J10.
2. If leakage protection occurs during configuration of a residual-current circuit breaker, disconnect
J10.