Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-158-
value is a percentage in relative to the rated current of
the motor.
Setting range: 0.0–200.0%
IF proportional
coefficient of
asynchronous
motor 2
When IF control is adopted for asynchronous motor 2,
this parameter is used to set the proportional coefficient
of the output current closed-loop control.
Setting range: 0–5000
IF integral
coefficient of
asynchronous
motor 2
When IF control is adopted for asynchronous motor 2,
this parameter is used to set the integral coefficient of
the output current closed-loop control.
Setting range: 0–5000
Starting frequency
point for switching
off IF mode for
asynchronous
motor 2
End frequency
point for switching
off IF mode for
asynchronous
motor 1
End frequency
point for switching
off IF mode for
asynchronous
motor 2
0x00–0x11
Ones: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
Tens: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
0: No function
1: Forward running
2: Reverse running
3: 3-wire control
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Running pause
9: External fault input
Function of HDIA
terminal