Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-242-
P28.22
EC PT1000
calibration lower
limit digital
0–4096
1100
P28.23
Detecting for
PT100/PT1000
disconnection from
EC
0x00–0x11
Ones place: PT100 disconnection detection
0: Disable
1: Enable
Tens place: PT1000 disconnection detection
0: Disable
1: Enable
0x00
P28.24
Enabling digital
calibration in EC
PT100/PT1000
temperature
detection
0–4
0: Disable
1: Enable PT100 lower limit digital calibration.
2: Enable PT100 upper limit digital calibration.
3: Enable PT1000 lower limit digital calibration.
4: Enable PT1000 upper limit digital calibration.
0
P28.25
Type of sensor for
AI/AO card to
detect motor
temperature
0–4
0: No temperature sensor
1: PT100
2: PT1000
3: KTY84
4: PTC
Note: Temperature is displayed through P19.21. To
measure temperature, switch the output of AO1 to
current, and connect one end of the temperature resistor
to AI1 and AO1, and the other end to GND.
0
P28.26
AI/AO detected
motor OH
protection
threshold
0.0–200.0°C
Note: When the motor temperature exceeds the
threshold, the VFD releases the OT alarm.
110.0°C
P28.27
AI/AO detected
motor OH pre-
alarm threshold
0.0–200.0°C
Note: When the motor temperature exceeds the value,
the DO terminal with function 48 (AI detected motor OH
pre-alarm) outputs a valid signal.
90.0°C