Frequency Inverter ST600 Series High-Performance Multifunction VFD Troubleshooting
-259-
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes,
replace the insertion port after
power down
C3-Er
[65] Communication
timeout occurred to the
expansion card in card
slot 3
There is no data transmission in
interfaces of card slot 3
Confirm whether the
expansion card inserted can
be supported;
Stabilize the expansion card
interfaces after power down,
and confirm whether fault still
occurs at next power-on;
Check whether the insertion
port is damaged, if yes,
replace the insertion port after
power down
E-DP
[29] PROFIBUS card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-NET
[30] Ethernet card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer
Check whether the
communication card wiring is
loose or dropped
E-CAN
[31] CANopen card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-PN
[57] PROFINET card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-CAT
[66] EtherCAT card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-BAC
[67] BACNet card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
E-DEV
[68] DeviceNet card
communication timeout
fault
There is no data transmission
between the communication card
and the host computer (or PLC)
Check whether the
communication card wiring is
loose or dropped
SECAN
[58] CAN master/slave
communication card
communication timeout
fault
There is no data transmission
between the CAN master and
slave communication cards
Check whether the
communication card wiring is
loose or dropped
S-Err
[69] CAN slave fault in
master/slave
synchronization
Fault occurred to one of the CAN
slave VFDs
Detect the CAN slave VFD
and analyze the
corresponding fault cause of
the VFD